OSHA Standard Requiring Fire Extinguisher in Construction (29 CFR 1926)--12/91
| Standard | Location | Type | Distance (feet) |
| 150(c)(1)(i) | Building Area | 2A | 100 |
| 150(c)(1)(iv) | Each Floor | 2A | ----- |
| 150(c)(1)(iv) | Multistory Bldg. | 2A | Adjacent to stairway |
| 150(c)(1)(vi) | 5 gallons of flammable/combustible or 5 lbs. of flammable gas | 10B | 50 |
| 151(c)(6) | Open yard storage | 2A or suitable | 100 |
| 152(d)(1) | Flammable Liquid | 20B | 10, Outside storage |
| 152(d)(2) | Outside Flammable Liquid Storage Area | 20B | 25-75 |
| 152(d)(4) | Vehicles used for dispensing or transporting flammable or combustible liquids | 20B:C | On vehicle |
| 152(g)(11) | Service or fuel area | 20B:C | 75 |
| 153(1) | LPG storage area | 20B:C | ----- |
| 352(d) | Welding, cutting or heating areas | Suitable | ----- |
| 550(a)(14)(i) | Crane cabs | 5B:C | On crane |
| 800(m)(8) | Tunnel machinery not using fire-resistant hydraulic fluid | 4A:40B:C | ----- |
| 800(m)(11) | Tunnel underground belt conveyors at head and tail pulley | 4A:40B:C | ----- |
| 902(i) | Vehicles used for transportation of explosives | 10A:B:C | ----- |
|